With
capability to undertake turnkey jobs in industrial electrification,
development of electrical lines, establishment of sub-stations, etc., we
solicit inquiries from corporates & institutional clients in India &
abroad.

Pin Insulators
We manufacture and supply high
performance pin insulators for various industrial applications. The pin
Insulators of one piece or multi piece design are widely used in low cost
distribution lines. The Multi-piece design makes these insulators very less
vulnerable to damage, as with one shell broken a multi-piece insulator can
generally withstand the line voltage for a considerable time without any
difficulty.
The different types of pin insulators available with us include 11 KV Pin
Insulators, 22 KV Pin Insulators and 33 KV Pin Insulators.
11 KV Pin Insulators
Standard Particulars
| Drawing No. |
Reeco PN-1104 |
Reeco PN-1103 |
Reeco PN-1102 |
| Highest System Voltage |
KV |
12 |
12 |
12 |
| Working Voltage |
KV |
11 |
11 |
11 |
| Creepage Distance Minimum |
mm |
320 |
230 |
230 |
| Visible Discharge Voltage |
KV |
9 |
9 |
9 |
| Mechanical Failing Load |
K N |
10 |
5 |
5 |
| Power Frequency
Withstand Voltage |
Wet |
KV |
35 |
35 |
35 |
| Dry |
KV |
60 |
40 |
40 |
| Power Frequency
Flashover Voltage |
Wet |
KV |
40 |
40 |
40 |
| Dry |
KV |
65 |
65 |
65 |
| Impulse Withstand Voltage |
KVp |
75 |
75 |
75 |
| Puncture Voltage |
KV |
105 |
105 |
105 |
| Lead Thimble as per IS:2486 (Part II) |
|
Small/Large |
Small/Large |
Small |
| Net Weight (approx.) |
Kg. |
1.8 |
1.5 |
1.25 |
| Specification as per IS:731, BS:137,
IEC:383 |
|
|
|
|
22 KV Pin Insulators
Standard Particulars
| Drawing No. |
Reeco PN-2201 |
Reeco PN-2202 |
| Highest System Voltage |
KV |
24 |
24 |
| Working Voltage |
KV |
22 |
22 |
| Creepage Distance Minimum |
mm |
430 |
565 |
| Visible Discharge Voltage |
KV |
18 |
18 |
| Mechanical Failing Load |
K N |
10 |
10 |
| Power Frequency
Withstand Voltage |
Wet |
| Dry |
| Power Frequency Flashover Voltage
|
Wet |
| Dry |
|
KV |
75 |
80 |
| KV |
90 |
95 |
| KV |
80 |
85 |
| KV |
95 |
100 |
| Impulse Withstand Voltage |
KVp |
170 |
185 |
| Puncture Voltage |
KV |
180 |
190 |
| Lead Thimble as per IS:2486 (Part II) |
|
Large |
Large |
| Net Weight (approx.) |
Kg. |
7.5 |
9.5 |
| Specification as per IS:731, BS:137, IEC:383 |
|
|
|
33 KV Pin Insulators
Standard Particulars
| Drawing No. |
Reeco PN-2201 |
Reeco PN-2202 |
| Highest System Voltage |
KV |
36 |
36 |
| Working Voltage |
KV |
33 |
33 |
| Creepage Distance Minimum |
mm |
58 |
685 |
| Visible Discharge Voltage |
KV |
27 |
27 |
| Mechanical Failing Load |
KVN |
10 |
10 |
| Power Frequency
Withstand Voltage |
Wet |
| Dry |
| Power Frequency Flashover Voltage
|
Wet |
| Dry |
|
KV |
55 |
70 |
| KV |
75 |
90 |
| KV |
60 |
75 |
| KV |
85 |
95 |
| Impulse Withstand Voltage |
KVp |
125 |
160 |
| Puncture Voltage |
KV |
140 |
170 |
| Lead Thimble as per IS:2486 (Part II) |
|
Large |
Large |
| Net Weight (approx.) |
Kg. |
5.0 |
7.0 |
| Specification as per IS:731, BS:137, IEC:383 |
|
|
|
Product Range